I returned mine. If the purpose of fuses is to protect circuits from overloads, they will not do their job. For fun, I put several of the following fuses in the .600 amp circuit: 0.1, 0.2, 0.25, 0.5. All fuses should have blown immediately, but all samples passed the test that should have destroyed them. The current in the circuit was checked with a Fluke 117 multimeter. The inrush current is about 600mA. The continuous current is about 280 mA. All samples of fuses, except 0.5A, should have blown only due to a constant current. The 0.5A fuse should have blown on startup as it is said to "burn quickly".